8e差流检测法的分布式直流接地巡检系统

第23卷第11期

电子测量与仪器学报

JoURNALoFELECTRoNlCMEAsUREMENTANDlNsTRUMENT

砀L23No.1l

36

2009年11月

基于差流检测法的分布式直流接地巡检系统冰

黄海宏全成黄锦

(合肥T业大学,合肥230009)

摘要:绝缘监察装置是变电站和发电厂用直流操作电源必备的检测装置。对传统的绝缘监测的方法的原理进行了分析,并指fl;其存在的问题。在此基础卜,对差流检测法的基本原理进行分析,其采用埘正负母线绝缘检测电阻的定时切换,形成不平衡桥,可检测出正负母线对地绝缘电阻;与直流漏电传感器相结合,可实现直流馈出支路绝缘故障的极性和阻值检测。介绍了以此为基础的分布式直流接地巡检系统的’I:作原理,该系统能准确定位绝缘电阻下降或接地分支,既可监测输}}{直流支路任意极性绝缘下降或接地故障,也可监测直流支路正极、负极绝缘同时F降的情况。该系统组态灵活,尤其适合监测范围大,分支回路多的直流电源系统。

关键词:直流电源系统;绝缘监察;差流检测法;分布式结构中图分类号:TM721.1TM855

文献标识码:A

国家标准学科分类代码:470.4017

DevelopmentofdistributedDCgroundingdetectingdifferentialcurrentdetecting

HuangHaihong

system

method

based

on

QuanChengHuangJin

(HefeiUniversityofTechnology,Hefei230009China)

Abstract:InsulationmonitoringdeviceisnecessarydetectingdeviceofDCoperationpowersupplyinsubstationsandpowerplants.Theprincipleofconventionalinsulationsupervisionandmeasurementwasanalyzed,andtheexistingproblems

are

discussed.Based

on

these

analyses,theprincipleofdifferentialcurrentmethodwasanalyzed.The

unbal—

ancedbridgeisformedbyswitchinginsulationdetectingresistancestopositivebusresistancestopositivebusandnegativebusgrounding

Call

andnegative

bus,sothegrounding

bedetected.Based

on

unbalancedbridge,thepolarityandthevalueof

ofdistributedDCgroundingdetect-

can

resistances

on

can

be

detectedbyusingleakcurrent

sensors.Theprinciple

ingsystembaseddifferentialcurrentdetectingmethodwasintroduced,thesystem

can

exactlydiscoverDCbranch

thathasinsulationfault.Itinsulationfaultsboth

on

not

onlydetectgroundingpolarityofanybranch,butalsoinspecttheinstancethathas

positiveoutputandnegative

output.Thesystemhasflexibleconfiguration,whichissuittoDC

powersuppliesthathaveexcessiveoutputbranchandlargeinspectingrange.

Keywords:DCpowersupplysystem;insulationmonitoring;differentialcurrentdetectingmethod;distributed

structure

运行的安全。由于直流系统分布广,元器件多,所处

环境各异,可能会出现绝缘下降,甚至一点接地现

象。与通信基站用48V直流电源的正输出与大地相连不同,电力用直流操作电源输出正、负母线均不接地,故一点绝缘下降或接地,对直流系统和直流负

发电厂和变电所直流系统是发电厂和变电所中

控制回路、信号回路、保护装置、自动装置及自动

化系统的操作电源,其可靠性直接影响到电力系统

本文于2009年8月收到。

・基金项目:合肥工业大学2009年度大学生创新性实验计划(编号:2009CXSY071)资助项目。

万方数据

第11期基于差流检测法的分布式直流接地巡检系统

37

荷工作无任何影响,但必须及时发现和消除,否则当出现另一点绝缘下降或接地,就会造成直流电源输出正负母线通过大地形成回路,可能会引起保护装置误动作,甚至直流断路器跳闸或熔断器熔断,导致二次回路失去直流工作电源,故电力用直流操作电源系统均安装绝缘监察装置。

2传统的绝缘检测系统

早期发电厂和变电站的直流系统采用电桥平衡

技术来检测接地故障,其原理如图1所示…。其中皿

和R.分别为正负直流母线对地电阻,尺为检测装置内部的检测电阻,两为继电器检测电阻。当风和n很大时,只有微小的不平衡电流流过风。当直流母线某一级的对地电阻下降到某一门槛值时,电桥失去平衡,有电流流过焉,继电器动作,绝缘监察装置发出接地报警信号。

正母线

大地

负母线

图1

平衡桥检测绝缘原理

Fig.1

Principleofdetectinginsulationwithbalancedbridge

发生绝缘故障后,现场运行维护人员对直流系统采取拉路寻找、分段处理的步骤,逐步确定接地支路。由平衡桥原理可知,该方法不能反映直流系统正、负母线绝缘均等下降的情况,且只能判断直流系统的整体绝缘状态,不能实现故障分支定位,当直流馈出支路较多时,采用拉路法会耗费较多的时间,要考虑直流缺电的影响,如对合闸回路,应考虑拉路后一段时间内不能合闸和重合闸的情况。特别是对直流控制电源,拉路前应采取必要措施防止直流失电可能引起继电保护、自动装置不正确动作,危及电力系统的安全运行【2J。故目前该方法只用于支路数不多、控制、继电保护、自动装置回路简单、自动化水平较低及对供电可靠性要求不高的35kV及以下变电站和10kV开闭所中的直流系统。

为实现不停电的支路查找要求,从20世纪90年

万方数据

代末开始,采用信号寻迹法的微机型直流接地巡检仪开始在l10kV及以上变电站和发电厂得到广泛应用。其在直流馈出支路安装毫安级的电流互感器(CT),如图2所示。

接直流负载I接直流负载2

接直流负载N

图2信号寻迹法原理图

Fig.2

Principleofsignaltrackingmethod

当该装置检测到正负母线对地绝缘电阻低于门槛值时,装置在正母线注入一个低频交流信号,在CT的二次侧检测各支路低频电流的幅值和相位,进

而计算出各支路的绝缘电阻口】。该方法成功地实现了不停电查找接地支路的要求,但须向被测直流系统施加交流信号,尽管其幅值与直流母线电压相比很

小,但对安全性要求很高的电力系统来说,施加的交流信号毕竟会带来不安全因素。而且其测量精度

受分布电容影响大f4J。对于分布电容较大的系统,对地容性漏电流远大于阻性漏电流,很难精确提取有

功分量,影响正确检测。若发生多支路同时接地情况,该装置不能同时检测出所有接地支路,只能检测出接地电流最小的支路,只有排除此支路的接地故障后,才能依次检出其他接地支路。为提高检测精度,在此基础上变频探测法得到应用,变频探测是向直流系统依次加入两个不同频率同幅值的交流信号进行检测【5】。从原理上看,该方法基本解决了受分布电容大小影响的不足,但当系统分布电容很大时,要求电流互感器有较大的动态范围和测量精度。这在实际工程中很难办到,而且该方法仍然对直流系统会造成一定的干扰【6】。由于目前发电厂和变电所直流系统均采用高频开关电源模块并联输出模式,信号寻迹法中向直流系统施加的低频交流信号易受到电源模块的高频开关信号的干扰,导致测量精度下降。

38

电子测量与仪器学报

第23卷

3差流检测法检测绝缘故障

差流检测法是较为新颖的方法,其利用不平衡桥检测母线绝缘状况,再结合直流漏电流传感器实现对分支故障进行检测。该方法无须向系统注入低频信号,对直流系统不会造成干扰,且与系统分布电容大小无关,检测灵敏度较高。

图3为不平衡桥检测母线绝缘状况的原理,其

中缸和疋为可控开关,尺为绝缘检测电阻。当缸闭合疋断开时,测量正母线对地电压为“+;当H断开n闭合时,测量负母线对地电压为“一;若正负母线

间电压为U。,则可得式(1):

坼一

R//qUmR//q+疋

R||R

Um

R//疋+q

对式(1)推导,可得式(2):

凡=Um--U+--U_R

(2)

足=.Um--U+--U_R

“上

根据式(2)所计算的绝缘电阻值,可判定直流系统绝缘状况,能判定绝缘下降的极性。由于是对&和疋定时切换,即使两极绝缘电阻同时均等下降,

此法也有效,克服了传统平衡桥测绝缘状况的弊端。

正母线

JF母线

虬l

大地

大地

甜一l

负母线负母线

图3

不平衡桥检测母线绝缘状况

Fig.3

Detectinginsulationofbuswithunbalancedbridge

为实现直流馈出支路绝缘下降查找功能,将图2中的电流互感器换成非接触式直流漏电流传感器,可检测出任一分支正负导线的流入与流出电流差值的大小与方向。

在鼠或疋闭合期间,若无绝缘电阻下降或接地

万方数据

故障,穿越漏电流传感器的正极电流L和负极电流L大小相等、方向相反,即L=L,两者的差值为零,则漏电传感器输出为0。

大地

大地

图4差流检测法检测馈出支路绝缘状况

Fig.4

Detectingmethoddetectinginsulationofoutput

branchwithdifferentialcurrent

鼠闭合疋断开时,若分支电路负极绝缘电阻

下降或接地,分支负极接地电阻为尺z一与正母线绝缘检测电阻R通过大地形成回路,分支电路负极存

在漏电流,穿越漏电流传感器的正极电流和负极电流之差为如一。E断开肛闭合时,若分支电路正极

绝缘电阻下降或接地,分支正极接地电阻为尺z十与负母线绝缘检测电阻尺通过大地形成回路,分支电路正极存在漏电流,穿越漏电流传感器的正极电流和负极电流之差为,Z+。根据各支路的直流漏电传感器是否输出为O和输出电压的极性即可判断出该

支路是否有接地故障和接地的极性。但具体接地的

电阻值的计算则要根据支路接地点的情况进行分

析和计算,其具体情况可按单支路接地和多支路接

地来区分。

jF母线

正母线

Ura大地

负母线

负母线

(a)(b)

图5单支路接地等效电路

Fig.5

Equivalentcircuitofsinglebranchgrounding

第11期基于差流检测法的分布式直流接地巡检系统

39

图5为单支路接地的等效电路,其模拟正负均接地的情况,图5(a)为缸闭合豇断开时的等效电路,图5(b)为墨.断开疋闭合时的等效电路。显然式(1)

中的“+=JOR,址=,z嘏,则通过推导式(2)可得式(3)。

图6为多支路出现接地故障的等效电路。先考~一虑多支路同极性接地的情况,图(a)为多支路负接地,

一一k一一k

k~一k

而正极无接地,即Rzl+一Rzn+为无穷大,且墨闭合疋

断开时的等效电路,则通过式(4)可计算出Rzl.~Rza一的具体数值。

RZ|-=型笺导趔

(4)

酝一=型气导趔

同理,当出现多支路正接地无负接地时,可根

(b)

图6多支路接地等效电路

Fig.6

Equivalentcircuitofseveralbranchgrounding

万方数据

据鼠断升疋闭合时测得的,Zl+~如+计算出尺zl+一

尺ZIl+的具体数值。

绝缘检测最复杂的情况是多支路正负均有接地,

图(b)是多支路正负均有接地且艮闭合疋断开时的等效电路。由于此时漏电传感器检测到的,zl一一坛一比实际流过如l一一尺ZIl一的电流数值要小,若应用式(4)

来具体计算RzrRz.一的数值,其结果比实际接地电

阻值要大。

下面对差流检测法检测馈出支路绝缘情况进行总结,如表1所示。

表1差流检测法检测馈出支路绝缘情况

Table1

Detectinginsulationofoutputbranchwithdifferential

current

detectingmethod

虽然在多支路正负均有接地故障时,差流检测法无法准确计算出各支路的接地电阻,但其仍然能进行接地故障支路定位和接地极性判断。而无论接地电阻数值大小,都应对该支路进行检修,故该缺点不影响差流检测法的具体应用。

4分布式直流接地巡检系统

目前,直流系统绝缘在线监测大多采用集中式的数据采集和处理系统。这种系统现场布线多,施工

复杂,采集点到微机多为小信号模拟量的传送,易

受电源现场的电磁干扰。当被监测直流系统范围很大时,问题尤为突出【71。

本次设计以差流检测法为基础,研制分布式直

AB

出1出8出l

出8

图7分布式直流接地巡检系统

Fig.7

DistributedDCgroundingdetectingsystem

-40・

电子测量与仪器学报第23卷

流接地巡检系统,系统由一台监测主机和若干测试单元组成,测试单元内置单片机,通过直流漏电流传感器采集各直流输出同路的直流漏电流,并将检测值通过RS485总线上传至监测主机。监测主机采用不平衡桥技术,计算正负母线对地绝缘电阻值,

结合各直流支路漏电流,定位接地支路,计算支路

绝缘电阻,其原理框图如图7所示。

其中测试单元内置单片机,其自带8路10位AD,可检测8个直流漏电传感器的输出电压。其原理框图如图8所示。

l篆勰翳1卜岖塑母一

l感器输出

1匕兰二二竺_’

似RXD

l篆黜墨8卜恒砷

荔TxD

拂:

l感器输出

’匕!二竺■

I/O

一黜普墓

图8测试单元原理框图

Fig.8

Schematicdiagramoftestunit

为解决负电压的检测问题,对漏电传感器的输出电压进行电压提升和滤波后再进入单片机的AD进行测量。其通过通讯站号测试电路设置唯一站号,

响应监测单元的召唤命令,将测得的各直流馈出支

路漏电流,Z+和弦上传给监测单元。

图9为监测单元结构框图。监测单元采用双微

处理器结构。微处理器1控制开关控制电路实现缸和疋的分时切换,并通过内置AD配合隔离电压采

集电路检测母线电压Um、正母线对地电压为虬和负母线对地电压为U一,通过485总线召唤各测试单元,获得各支路漏电流数据,计算母线对地电阻和直流馈出各支路对地电阻,将故障信息传给微处理器2。微处理器2为双串口的51派生单片机,配置液晶显示模块和键盘组成的人机交互界面,实现数据显示和参数设置,并通过485总线将测试单元数目和告警电阻阀值等参数传给微处理器1。同时可通过上行的232/485口与上位机进行通讯,将测得的绝缘数据实现远传。

电压采集电路和开关控制电路如图10所示。其中AQV210为固态继电器,其受微处理器1的I/O口控制,切换检测电阻尺l和尺2分时与正、负母线相连接。尺3、风与尺5、R6组成分压电路,通过精密隔离

万方数据

运放IS0124对正、负母线对地电压进行检测【8I。

图9监测单元原理框图

Fig.9

Schematicdiagramofmonitoringunit

卜母线

负母线

图10电压采集电路和开关控制电路

Fig.10

Voltagedetectingcircuitandswitchcontrol

circuit

实验

选用直流漏电传感器LDCS.10mA,其输出电压±5

v对应差流_10mA。使用稳压电源输出48V模拟

正负母线,用万用表测量所有选用的电阻,选用两个30kQ电阻(实测为29.8kQ)作为母线检测电阻,进行母线接地和分支接地实验。

实验数据表明,实验方法可有效检测出正负母线接地电阻均等下降的情况。

第11期基于差流检测法的分布式直流接地巡检系统

实验数据表明,实验方法可有效检测出单支路

正负均接地的情况。

表2母线接地检测

Table2

Detectionofbusgrounding

表3单分支接地检测

Table3

Detectionofsingleoutputbranchgrounding

表4多分支负接地检测

Table4

Detectionofseveraloutputbranch

grounding

实验数据表明,实验方法可有效检测出多支路同极性均接地的情况。

经测试表明,将母线检测电阻降为10kfl时,测量精度可提高。

6结论

基于差流检测法的分布式直流接地巡检系统具有组态灵活,可靠性高的特点。系统能正确反映绝缘电阻下降:既能判定母线绝缘电阻下降的极性,也能确定母线的绝缘电阻值;能准确定位绝缘电阻下

降或接地分支,既可监测输出直流支路任意极性绝

缘下降或接地故障,也可监测直流支路正极、负极绝缘同时下降的情况。其采用分布式结构,很好地解决了集中式绝缘在线监测系统所存在的问题,尤其适用于监测范围大,分支回路多的情况。

参考文献:

【l】

赵兵等.直流系统微机型绝缘监察装置问题的探讨【J】.广东电力,2009,22(4):43-45.

ZHAOB.Problemsofmicrocomputer-basedinsulationmonitorforDC

system[J].GuangdongElectricPoweL

2009,22(4):43-45.

万方数据

【2】

杨伟.直流系统绝缘监察装置的探索【J】.内蒙古电力技术,2005,23(3):22.24,39.

YANGWei.Discussion

on

insulation

inspectionappa-

ramsforDCsystem[J].InnerMongoliaElectricPoweL

2005,23(3):22—24,39.

【3】

王广柱.直流系统绝缘自动监测仪研制[J】.电子测量与仪器学报,1998,12(2):51.54.WANG

GZH.Thedevelopmentofautomaticinsulation

monitorforDC

systemlJ].JournalofElectronicMeas-

urementandInstrumenL

1998,12(2):51-54.

【4】李立伟.直流系统接地电阻检测仪的研究与实现[J】.测控技术,2002,21(10):27.29.ULW.Research

andrealizationoftheinsulatingresis—

tance

measuringinstrumentinDCsystem[J].Measure-

ment&Control

Technology,2002,21(10):27-29.

【5】曾刚.改进变频法检测直流接地故障【J】.电工技术,

2004.8:58—59.

ZENGG.Improvingfrequencychangingmethod

totest

DCgroundingfailure[J].ElectricEngineering.2004。8:

58—59.

【6】尹星光.直流接地巡检装置误、漏选线问题分析[J】.继电器,2008,36(10):83.85.

YINXG.Analysis

on

thewrongly

or

missed

lineselec—

tionwithDCgroundfaultpatroldevice[J].Relay,2008,

36(10):83—85.

【7】

苏小林.分布式直流系统绝缘在线监测的研究【J】.微计算机信息,2005,21(8):86.88.

SU

XL.Research

on

distributed

on—lineinsulation

supervisionandmeasurementforDC

systems[J].Control

&Automation,2005,21(8):86-88.

【8】

何玉锐.基于不平衡与平衡桥结合的直流绝缘监察技术[J】.电力科学与工程,2007,23(3):30-32.

HEYR.DCsysteminsulationmonitoringtechnologybased

on

unbalance

and

balance

bridge[J].PowerSci-

ence

and

Engineering,2007,23(3):30・32.

作者简介:

黄海宏:1973年出生,分别于1996年和1999年获合肥工业大学学士和硕士学位。现为合肥T业大学副教授,主要研究方向为电力电子技术和自动控制。

E—mail:hhaihon9741@tom.tom

HuangHaihong

Wasbornin1973.Hereceivedthebachelor

degree

andthemasterdegreefromHefeiuniversityof

technol—

ogyin1996andl999respectively.NowheisassociateprofessorinHefeiuniversityof

technology.His

researchinterestsinclude

electroniCSandautomation.

power

第23卷第11期

电子测量与仪器学报

JoURNALoFELECTRoNlCMEAsUREMENTANDlNsTRUMENT

砀L23No.1l

36

2009年11月

基于差流检测法的分布式直流接地巡检系统冰

黄海宏全成黄锦

(合肥T业大学,合肥230009)

摘要:绝缘监察装置是变电站和发电厂用直流操作电源必备的检测装置。对传统的绝缘监测的方法的原理进行了分析,并指fl;其存在的问题。在此基础卜,对差流检测法的基本原理进行分析,其采用埘正负母线绝缘检测电阻的定时切换,形成不平衡桥,可检测出正负母线对地绝缘电阻;与直流漏电传感器相结合,可实现直流馈出支路绝缘故障的极性和阻值检测。介绍了以此为基础的分布式直流接地巡检系统的’I:作原理,该系统能准确定位绝缘电阻下降或接地分支,既可监测输}}{直流支路任意极性绝缘下降或接地故障,也可监测直流支路正极、负极绝缘同时F降的情况。该系统组态灵活,尤其适合监测范围大,分支回路多的直流电源系统。

关键词:直流电源系统;绝缘监察;差流检测法;分布式结构中图分类号:TM721.1TM855

文献标识码:A

国家标准学科分类代码:470.4017

DevelopmentofdistributedDCgroundingdetectingdifferentialcurrentdetecting

HuangHaihong

system

method

based

on

QuanChengHuangJin

(HefeiUniversityofTechnology,Hefei230009China)

Abstract:InsulationmonitoringdeviceisnecessarydetectingdeviceofDCoperationpowersupplyinsubstationsandpowerplants.Theprincipleofconventionalinsulationsupervisionandmeasurementwasanalyzed,andtheexistingproblems

are

discussed.Based

on

these

analyses,theprincipleofdifferentialcurrentmethodwasanalyzed.The

unbal—

ancedbridgeisformedbyswitchinginsulationdetectingresistancestopositivebusresistancestopositivebusandnegativebusgrounding

Call

andnegative

bus,sothegrounding

bedetected.Based

on

unbalancedbridge,thepolarityandthevalueof

ofdistributedDCgroundingdetect-

can

resistances

on

can

be

detectedbyusingleakcurrent

sensors.Theprinciple

ingsystembaseddifferentialcurrentdetectingmethodwasintroduced,thesystem

can

exactlydiscoverDCbranch

thathasinsulationfault.Itinsulationfaultsboth

on

not

onlydetectgroundingpolarityofanybranch,butalsoinspecttheinstancethathas

positiveoutputandnegative

output.Thesystemhasflexibleconfiguration,whichissuittoDC

powersuppliesthathaveexcessiveoutputbranchandlargeinspectingrange.

Keywords:DCpowersupplysystem;insulationmonitoring;differentialcurrentdetectingmethod;distributed

structure

运行的安全。由于直流系统分布广,元器件多,所处

环境各异,可能会出现绝缘下降,甚至一点接地现

象。与通信基站用48V直流电源的正输出与大地相连不同,电力用直流操作电源输出正、负母线均不接地,故一点绝缘下降或接地,对直流系统和直流负

发电厂和变电所直流系统是发电厂和变电所中

控制回路、信号回路、保护装置、自动装置及自动

化系统的操作电源,其可靠性直接影响到电力系统

本文于2009年8月收到。

・基金项目:合肥工业大学2009年度大学生创新性实验计划(编号:2009CXSY071)资助项目。

万方数据

第11期基于差流检测法的分布式直流接地巡检系统

37

荷工作无任何影响,但必须及时发现和消除,否则当出现另一点绝缘下降或接地,就会造成直流电源输出正负母线通过大地形成回路,可能会引起保护装置误动作,甚至直流断路器跳闸或熔断器熔断,导致二次回路失去直流工作电源,故电力用直流操作电源系统均安装绝缘监察装置。

2传统的绝缘检测系统

早期发电厂和变电站的直流系统采用电桥平衡

技术来检测接地故障,其原理如图1所示…。其中皿

和R.分别为正负直流母线对地电阻,尺为检测装置内部的检测电阻,两为继电器检测电阻。当风和n很大时,只有微小的不平衡电流流过风。当直流母线某一级的对地电阻下降到某一门槛值时,电桥失去平衡,有电流流过焉,继电器动作,绝缘监察装置发出接地报警信号。

正母线

大地

负母线

图1

平衡桥检测绝缘原理

Fig.1

Principleofdetectinginsulationwithbalancedbridge

发生绝缘故障后,现场运行维护人员对直流系统采取拉路寻找、分段处理的步骤,逐步确定接地支路。由平衡桥原理可知,该方法不能反映直流系统正、负母线绝缘均等下降的情况,且只能判断直流系统的整体绝缘状态,不能实现故障分支定位,当直流馈出支路较多时,采用拉路法会耗费较多的时间,要考虑直流缺电的影响,如对合闸回路,应考虑拉路后一段时间内不能合闸和重合闸的情况。特别是对直流控制电源,拉路前应采取必要措施防止直流失电可能引起继电保护、自动装置不正确动作,危及电力系统的安全运行【2J。故目前该方法只用于支路数不多、控制、继电保护、自动装置回路简单、自动化水平较低及对供电可靠性要求不高的35kV及以下变电站和10kV开闭所中的直流系统。

为实现不停电的支路查找要求,从20世纪90年

万方数据

代末开始,采用信号寻迹法的微机型直流接地巡检仪开始在l10kV及以上变电站和发电厂得到广泛应用。其在直流馈出支路安装毫安级的电流互感器(CT),如图2所示。

接直流负载I接直流负载2

接直流负载N

图2信号寻迹法原理图

Fig.2

Principleofsignaltrackingmethod

当该装置检测到正负母线对地绝缘电阻低于门槛值时,装置在正母线注入一个低频交流信号,在CT的二次侧检测各支路低频电流的幅值和相位,进

而计算出各支路的绝缘电阻口】。该方法成功地实现了不停电查找接地支路的要求,但须向被测直流系统施加交流信号,尽管其幅值与直流母线电压相比很

小,但对安全性要求很高的电力系统来说,施加的交流信号毕竟会带来不安全因素。而且其测量精度

受分布电容影响大f4J。对于分布电容较大的系统,对地容性漏电流远大于阻性漏电流,很难精确提取有

功分量,影响正确检测。若发生多支路同时接地情况,该装置不能同时检测出所有接地支路,只能检测出接地电流最小的支路,只有排除此支路的接地故障后,才能依次检出其他接地支路。为提高检测精度,在此基础上变频探测法得到应用,变频探测是向直流系统依次加入两个不同频率同幅值的交流信号进行检测【5】。从原理上看,该方法基本解决了受分布电容大小影响的不足,但当系统分布电容很大时,要求电流互感器有较大的动态范围和测量精度。这在实际工程中很难办到,而且该方法仍然对直流系统会造成一定的干扰【6】。由于目前发电厂和变电所直流系统均采用高频开关电源模块并联输出模式,信号寻迹法中向直流系统施加的低频交流信号易受到电源模块的高频开关信号的干扰,导致测量精度下降。

38

电子测量与仪器学报

第23卷

3差流检测法检测绝缘故障

差流检测法是较为新颖的方法,其利用不平衡桥检测母线绝缘状况,再结合直流漏电流传感器实现对分支故障进行检测。该方法无须向系统注入低频信号,对直流系统不会造成干扰,且与系统分布电容大小无关,检测灵敏度较高。

图3为不平衡桥检测母线绝缘状况的原理,其

中缸和疋为可控开关,尺为绝缘检测电阻。当缸闭合疋断开时,测量正母线对地电压为“+;当H断开n闭合时,测量负母线对地电压为“一;若正负母线

间电压为U。,则可得式(1):

坼一

R//qUmR//q+疋

R||R

Um

R//疋+q

对式(1)推导,可得式(2):

凡=Um--U+--U_R

(2)

足=.Um--U+--U_R

“上

根据式(2)所计算的绝缘电阻值,可判定直流系统绝缘状况,能判定绝缘下降的极性。由于是对&和疋定时切换,即使两极绝缘电阻同时均等下降,

此法也有效,克服了传统平衡桥测绝缘状况的弊端。

正母线

JF母线

虬l

大地

大地

甜一l

负母线负母线

图3

不平衡桥检测母线绝缘状况

Fig.3

Detectinginsulationofbuswithunbalancedbridge

为实现直流馈出支路绝缘下降查找功能,将图2中的电流互感器换成非接触式直流漏电流传感器,可检测出任一分支正负导线的流入与流出电流差值的大小与方向。

在鼠或疋闭合期间,若无绝缘电阻下降或接地

万方数据

故障,穿越漏电流传感器的正极电流L和负极电流L大小相等、方向相反,即L=L,两者的差值为零,则漏电传感器输出为0。

大地

大地

图4差流检测法检测馈出支路绝缘状况

Fig.4

Detectingmethoddetectinginsulationofoutput

branchwithdifferentialcurrent

鼠闭合疋断开时,若分支电路负极绝缘电阻

下降或接地,分支负极接地电阻为尺z一与正母线绝缘检测电阻R通过大地形成回路,分支电路负极存

在漏电流,穿越漏电流传感器的正极电流和负极电流之差为如一。E断开肛闭合时,若分支电路正极

绝缘电阻下降或接地,分支正极接地电阻为尺z十与负母线绝缘检测电阻尺通过大地形成回路,分支电路正极存在漏电流,穿越漏电流传感器的正极电流和负极电流之差为,Z+。根据各支路的直流漏电传感器是否输出为O和输出电压的极性即可判断出该

支路是否有接地故障和接地的极性。但具体接地的

电阻值的计算则要根据支路接地点的情况进行分

析和计算,其具体情况可按单支路接地和多支路接

地来区分。

jF母线

正母线

Ura大地

负母线

负母线

(a)(b)

图5单支路接地等效电路

Fig.5

Equivalentcircuitofsinglebranchgrounding

第11期基于差流检测法的分布式直流接地巡检系统

39

图5为单支路接地的等效电路,其模拟正负均接地的情况,图5(a)为缸闭合豇断开时的等效电路,图5(b)为墨.断开疋闭合时的等效电路。显然式(1)

中的“+=JOR,址=,z嘏,则通过推导式(2)可得式(3)。

图6为多支路出现接地故障的等效电路。先考~一虑多支路同极性接地的情况,图(a)为多支路负接地,

一一k一一k

k~一k

而正极无接地,即Rzl+一Rzn+为无穷大,且墨闭合疋

断开时的等效电路,则通过式(4)可计算出Rzl.~Rza一的具体数值。

RZ|-=型笺导趔

(4)

酝一=型气导趔

同理,当出现多支路正接地无负接地时,可根

(b)

图6多支路接地等效电路

Fig.6

Equivalentcircuitofseveralbranchgrounding

万方数据

据鼠断升疋闭合时测得的,Zl+~如+计算出尺zl+一

尺ZIl+的具体数值。

绝缘检测最复杂的情况是多支路正负均有接地,

图(b)是多支路正负均有接地且艮闭合疋断开时的等效电路。由于此时漏电传感器检测到的,zl一一坛一比实际流过如l一一尺ZIl一的电流数值要小,若应用式(4)

来具体计算RzrRz.一的数值,其结果比实际接地电

阻值要大。

下面对差流检测法检测馈出支路绝缘情况进行总结,如表1所示。

表1差流检测法检测馈出支路绝缘情况

Table1

Detectinginsulationofoutputbranchwithdifferential

current

detectingmethod

虽然在多支路正负均有接地故障时,差流检测法无法准确计算出各支路的接地电阻,但其仍然能进行接地故障支路定位和接地极性判断。而无论接地电阻数值大小,都应对该支路进行检修,故该缺点不影响差流检测法的具体应用。

4分布式直流接地巡检系统

目前,直流系统绝缘在线监测大多采用集中式的数据采集和处理系统。这种系统现场布线多,施工

复杂,采集点到微机多为小信号模拟量的传送,易

受电源现场的电磁干扰。当被监测直流系统范围很大时,问题尤为突出【71。

本次设计以差流检测法为基础,研制分布式直

AB

出1出8出l

出8

图7分布式直流接地巡检系统

Fig.7

DistributedDCgroundingdetectingsystem

-40・

电子测量与仪器学报第23卷

流接地巡检系统,系统由一台监测主机和若干测试单元组成,测试单元内置单片机,通过直流漏电流传感器采集各直流输出同路的直流漏电流,并将检测值通过RS485总线上传至监测主机。监测主机采用不平衡桥技术,计算正负母线对地绝缘电阻值,

结合各直流支路漏电流,定位接地支路,计算支路

绝缘电阻,其原理框图如图7所示。

其中测试单元内置单片机,其自带8路10位AD,可检测8个直流漏电传感器的输出电压。其原理框图如图8所示。

l篆勰翳1卜岖塑母一

l感器输出

1匕兰二二竺_’

似RXD

l篆黜墨8卜恒砷

荔TxD

拂:

l感器输出

’匕!二竺■

I/O

一黜普墓

图8测试单元原理框图

Fig.8

Schematicdiagramoftestunit

为解决负电压的检测问题,对漏电传感器的输出电压进行电压提升和滤波后再进入单片机的AD进行测量。其通过通讯站号测试电路设置唯一站号,

响应监测单元的召唤命令,将测得的各直流馈出支

路漏电流,Z+和弦上传给监测单元。

图9为监测单元结构框图。监测单元采用双微

处理器结构。微处理器1控制开关控制电路实现缸和疋的分时切换,并通过内置AD配合隔离电压采

集电路检测母线电压Um、正母线对地电压为虬和负母线对地电压为U一,通过485总线召唤各测试单元,获得各支路漏电流数据,计算母线对地电阻和直流馈出各支路对地电阻,将故障信息传给微处理器2。微处理器2为双串口的51派生单片机,配置液晶显示模块和键盘组成的人机交互界面,实现数据显示和参数设置,并通过485总线将测试单元数目和告警电阻阀值等参数传给微处理器1。同时可通过上行的232/485口与上位机进行通讯,将测得的绝缘数据实现远传。

电压采集电路和开关控制电路如图10所示。其中AQV210为固态继电器,其受微处理器1的I/O口控制,切换检测电阻尺l和尺2分时与正、负母线相连接。尺3、风与尺5、R6组成分压电路,通过精密隔离

万方数据

运放IS0124对正、负母线对地电压进行检测【8I。

图9监测单元原理框图

Fig.9

Schematicdiagramofmonitoringunit

卜母线

负母线

图10电压采集电路和开关控制电路

Fig.10

Voltagedetectingcircuitandswitchcontrol

circuit

实验

选用直流漏电传感器LDCS.10mA,其输出电压±5

v对应差流_10mA。使用稳压电源输出48V模拟

正负母线,用万用表测量所有选用的电阻,选用两个30kQ电阻(实测为29.8kQ)作为母线检测电阻,进行母线接地和分支接地实验。

实验数据表明,实验方法可有效检测出正负母线接地电阻均等下降的情况。

第11期基于差流检测法的分布式直流接地巡检系统

实验数据表明,实验方法可有效检测出单支路

正负均接地的情况。

表2母线接地检测

Table2

Detectionofbusgrounding

表3单分支接地检测

Table3

Detectionofsingleoutputbranchgrounding

表4多分支负接地检测

Table4

Detectionofseveraloutputbranch

grounding

实验数据表明,实验方法可有效检测出多支路同极性均接地的情况。

经测试表明,将母线检测电阻降为10kfl时,测量精度可提高。

6结论

基于差流检测法的分布式直流接地巡检系统具有组态灵活,可靠性高的特点。系统能正确反映绝缘电阻下降:既能判定母线绝缘电阻下降的极性,也能确定母线的绝缘电阻值;能准确定位绝缘电阻下

降或接地分支,既可监测输出直流支路任意极性绝

缘下降或接地故障,也可监测直流支路正极、负极绝缘同时下降的情况。其采用分布式结构,很好地解决了集中式绝缘在线监测系统所存在的问题,尤其适用于监测范围大,分支回路多的情况。

参考文献:

【l】

赵兵等.直流系统微机型绝缘监察装置问题的探讨【J】.广东电力,2009,22(4):43-45.

ZHAOB.Problemsofmicrocomputer-basedinsulationmonitorforDC

system[J].GuangdongElectricPoweL

2009,22(4):43-45.

万方数据

【2】

杨伟.直流系统绝缘监察装置的探索【J】.内蒙古电力技术,2005,23(3):22.24,39.

YANGWei.Discussion

on

insulation

inspectionappa-

ramsforDCsystem[J].InnerMongoliaElectricPoweL

2005,23(3):22—24,39.

【3】

王广柱.直流系统绝缘自动监测仪研制[J】.电子测量与仪器学报,1998,12(2):51.54.WANG

GZH.Thedevelopmentofautomaticinsulation

monitorforDC

systemlJ].JournalofElectronicMeas-

urementandInstrumenL

1998,12(2):51-54.

【4】李立伟.直流系统接地电阻检测仪的研究与实现[J】.测控技术,2002,21(10):27.29.ULW.Research

andrealizationoftheinsulatingresis—

tance

measuringinstrumentinDCsystem[J].Measure-

ment&Control

Technology,2002,21(10):27-29.

【5】曾刚.改进变频法检测直流接地故障【J】.电工技术,

2004.8:58—59.

ZENGG.Improvingfrequencychangingmethod

totest

DCgroundingfailure[J].ElectricEngineering.2004。8:

58—59.

【6】尹星光.直流接地巡检装置误、漏选线问题分析[J】.继电器,2008,36(10):83.85.

YINXG.Analysis

on

thewrongly

or

missed

lineselec—

tionwithDCgroundfaultpatroldevice[J].Relay,2008,

36(10):83—85.

【7】

苏小林.分布式直流系统绝缘在线监测的研究【J】.微计算机信息,2005,21(8):86.88.

SU

XL.Research

on

distributed

on—lineinsulation

supervisionandmeasurementforDC

systems[J].Control

&Automation,2005,21(8):86-88.

【8】

何玉锐.基于不平衡与平衡桥结合的直流绝缘监察技术[J】.电力科学与工程,2007,23(3):30-32.

HEYR.DCsysteminsulationmonitoringtechnologybased

on

unbalance

and

balance

bridge[J].PowerSci-

ence

and

Engineering,2007,23(3):30・32.

作者简介:

黄海宏:1973年出生,分别于1996年和1999年获合肥工业大学学士和硕士学位。现为合肥T业大学副教授,主要研究方向为电力电子技术和自动控制。

E—mail:hhaihon9741@tom.tom

HuangHaihong

Wasbornin1973.Hereceivedthebachelor

degree

andthemasterdegreefromHefeiuniversityof

technol—

ogyin1996andl999respectively.NowheisassociateprofessorinHefeiuniversityof

technology.His

researchinterestsinclude

electroniCSandautomation.

power


相关内容

  • 直流系统接地故障原因分析及处理办法
  • 直流系统接地故障原因分析及处理办法 摘要:在变电站运行管理中,直流系统发挥着重要作用,直流系 统的故障会造成控制回路.信号回路.继电保护.自动装置等装置 不正确动作,本文分析了变电站直流系统接地的原因及危害,列举 了如单点接地.多点接地等情况分析和查找方法,提供了一些直流 查找的实际工作技巧,是变电 ...

  • 直流系统接地检测
  • 第17卷第1期电力系统及其自动化学报V o l . 17N o. 1 2005年2月P roceedings of the CSU 2EPSA Feb . 2005 直流系统接地检测 ① 张 毅, 张 泉, 李永丽 (天津大学电气与自动化工程学院, 天津300072) 摘要:直流系统接地在线检测装置 ...

  • 基站代维方案
  • 中国移动基站代维服务方案 服务单位: 项目负责人: 片区负责人: 1 项目代维服务方案 1.1 移动基站代维和发电服务执行组织结构 图:基站集中化管理代维组织架构图(此表为标准化表格,人员配备可 根据项目需要进行调整) 移动基站代维组织架构将遵从统一的"集中化管理模式",如上图所 ...

  • 315话光伏电站:这些问题不解决,光伏行业没希望!
  • tes 光伏回暖,'钱途'可期,光伏电站投资再次吸引了业内外大量资本的关注.但在一片叫好声中,对一个行业的参与者而言,探究其加速生长背后的理性与客观,应远比喝彩和跟风更为有力.昨天是'3·15国际消费者权益日',我们就一起来谈谈光伏电站质量问题. 过去的一年里,严重的电站质量问题层出不穷:组件负偏差 ...

  • 什么叫馈线和直流屏环网柜
  • 馈电线 电源端向负载供电的电馈电线路. 还有一种是进线回路,它有出线是到各个分柜的. 比如,高压有二路进线, 有四台变压器出线, 那从供电局过来的二根总线接的柜就叫进线, 变压器出线的柜就叫馈线,还有计量柜,PT柜等. 馈电线中的"馈"字就是"送"的意思,因此 ...

  • [微·干货]如此全面.详细的光伏电站运维手册,值得收藏!
  • 光伏电站这个领域,很明显,在即将进入后光伏时代之际,电站的运营.维护.托管业务将成为光伏电站的主旋律.而电站运营效率和效果将直接影响光伏电站的运行稳定性及发电量.对于计划长期持有光伏电站的业主来说,光伏电站的运营维护就显得十分重要和迫切了.运维业务的延伸和拓展也将成为光伏系统集成商的必争之地. 优质 ...

  • 3监控模块
  • 第三章 监控系统 3.1 概述 PSM-E20C 电力电源监控模块可应用于10~500KV以下变电站.电厂.各类用户变和其他需要直流供电的场合.配合HP 系列电力充电模块及其他采集模块(电池巡检.绝缘检测.开关检测模块),可完成智能化电池管理和直流系统监测及告警.PSM-E20C 监控模块具备远程管 ...

  • 风电场培训考试题一(答案)
  • 风电场培训考试题一 姓名: 考试时间: 成绩: 一. 判断题(每题1分,共10分) 1. 风力发电机组至少应具备两种不同形式的.能独立有效控制的制动系统.( √ ) 2. 为防止人身因电气设备绝缘损坏而遭受触电,将电气设备的金属外壳与接地体连接就叫保护接地.( √ ) 3. 风电机组偏航电机中一般都 ...

  • 小区覆盖系统维护要求
  • 小区覆盖系统日常维护办法(试行) 第一章 总 则 一. 小区覆盖系统构成:小区覆盖系统是移动通信网的一个组成部分,主要由分布式天线系统.基站系 统.传输系统及附属设备构成. 二. 小区覆盖维护目的:移动通信小区覆盖系统维护的最终目标是保证设备处于最佳运行状态,使其运 行服务质量能够满足用户业务使用需 ...