影响三级生物安全实验室性能的相关问题研究(终稿)

影响三级生物安全实验室性能的相关问题研究

黄征 李江龙 王力 凌继红 邢金城 周志航 涂光备

1 江苏苏净集团 2 天津大学环境学院

摘 要 本文对三级生物安全实验室中一更压力和安全门密封性对主实验室洁净度的影响,以及实验室运行工况转换与排风机故障切换时保持合理压力梯度的手段等问题进行了分析研究。通过实验总结出:一更保持非负压状态即可不影响主实验室的洁净度,而安全门的密封性对实验室污染区洁净度影响很大;采用设置在送风阀风量突变条件的定排风量控制,在工况转换和风机故障切换时能够维持实验室合理的压力梯度。

关键词 生物安全实验室 正压保护 工况转换 风机切换 定排风量控制

1

2

1

2

2

2

2

Research of the Problems that Affect the Capability of

Level-3 Biosafety Laboratory

By Huang Zheng, Li Jianglong, Wang Li, Ling Jihong, Xing jincheng, Zhou Zhihang and Tu Guangbei

Abstract The article summarizes the research process of the positive (or common) pressure protection in First Changeroom and the airproof of exit door, which may influence the indoor cleanliness, and also gives some methods on how to maintain the pressure gradient when the operation condition changes and the exhaust fan switches affected by sudden malfunction. One conclusion is that the pressure of First Changeroom has no influence on the cleanliness of the main room, but the airproof of exit door affects the indoor cleanliness badly, so a good airproof exit door is necessary. The Other conclusion is that by the help of the control system that keeps exhaust volume constant and decreases the supply air fast with the rising of indoor pressure, the reasonable pressure gradient in contaminative zone can be maintained when the operation condition changes or the exhaust fan switches.

Keywords Level-3 Boisafety Laboratory, Positive pressure protection, Operation condition change, Fan switch, Constant exhaust volume control

1 引言

2003年SARS 病毒大流行后,我国生物安全实验室的建设出现了前所未有的发展。国家陆续发布了关于微生物实验室建设与管理的相关条例与规范,并建立了实验室国家认可制度。2004年施行的《病原微生物实验室生物安全管理条例》[1]规定:可以进行高致病性病原微生物实验活动的三、四级生物安全实验室必须满足下述要求:①符合国家生物安全实验室建筑技术规范;②通过实验室国家认可;③工程质量经建筑主管部门依法检测验收合格。

相关资料统计,目前,我国已建成和在建的三级生物安全实验室有上百家,而通过实验室国家认可的三级实验室仅16家,大部分实验室在建成后不能通过国家认可,究其原因

主要有两点:一方面,建筑设计或承建单位对生物安全实验室的认识不足,致使设计施工过程中存在一些缺陷,另一方面,生物安全实验室压差控制策略还存在着一些有待突破的难点。鉴于此,苏净集团和天津大学依据共同承担的江苏省科技攻关课题,建造了一个1:1的生物安全实验室模型,对三级生物安全实验室施工及压差控制中存在的一些问题进行了研究。本文仅针对实验室的洁净度和压差控制问题进行探讨如下,希望在三级生物安全实验室建设和运行方面能为相关单位提供一些参考。

22

本课题组搭建的模型实验室总面积150m ,其中主实验室面积26m ,其余为辅助用房,包括参观走廊、监控室、洗消间、换鞋间、一更、淋浴间、二更、缓冲一、隔离走廊、缓冲二等,洁净度等级除主实验室为ISO 7级外,其余房间均为ISO 8级[2],[3],[4],[5]。平面布局如图1

所示。

图1 三级生物安全实验室平面布局图

2 洁净度的控制

在负压洁净室内,除了过滤器的过滤效率和气流分布[6]外,影响室内洁净度的主要因素是换气次数和由非洁净区渗入的空气量。在相同的换气次数下,由非洁净区渗入的风量越小,对室内洁净度越有利。对于生物安全实验室区域,来自非洁净区的渗入风量主要通过一更门和安全门进入,因此,我们重点对这两个方面进行了实验研究。 2.1 正压保护与零压保护对洁净度的影响

在实验室的平面布局中,实验室洁净区域通过一更与非洁净区连通。一更的负压将增加渗入室内的空气量,进而影响室内的洁净度,因此,人们通常将一更相对于非洁净区的压力设置为微正压或零压以阻止室外未经净化的空气渗入洁净区,称为正压或零压保护。相关参考文献[7],[8]认为,正压隔离对主实验室的洁净度更为有利。为了对比正压保护和零压保护的效果,我们分别对一更正压和零压情况下各房间的室内粒子浓度进行了多次检测,主要房间检测结果见表1、图2~4。

表1 正压和零压保护下主要房间粒子浓度的测试值 单位: pcs/m3房间名称 主实验室 缓冲一 二更

工 况 正压 零压 正压 零压 正压 零压

0.3um 0.5um 1um 35336 31449 26502 38163 65018 73145

2um 23322 24735 20495 31802 53710 55830

3um 9894 14488

11307 15194 25442

32862

5um 1060 1060 2473 2473 3180 6007

197173 195406 135689 315194 178799 162898 342049 225795

图2 主实验室各粒径粒子浓度 图3 缓冲一各粒径粒子浓度

图4 二更各粒径粒子浓度

从测试数据可以看出,在一更相对于非洁净区为零压的情况下,二更和缓冲一测得的空气各粒径粒子浓度比在一更保持正压情况下大,而主实验室由于与外界有多重缓冲,各粒径粒子浓度在两种工况下相差不大,即一更的正压和零压仅影响相邻的二更和缓冲二的室内粒子浓度,但是对主实验室的空气洁净度不产生显著影响,由此可见,一更采取正压保护的观点,有待进一步研究和商榷。

2.2 安全门的密封性对实验室洁净度的影响

基于消防安全方面考虑,三级生物安全实验室须在半污染区设置安全通道(即安全门)作为紧急出口。安全门一般设置在隔离走廊,距离主实验室较近,由于隔离走廊的负压较大(-30Pa ),导致大量未经过滤的室外空气经安全门渗入室内,不仅影响了隔离走廊的洁净度,还影响到缓冲二和主实验室的洁净度。我们在主实验室换气次数为20 AC/h,安全门采用不同的密封措施下分别对隔离走廊、缓冲二、主实验室进行了洁净度测试,测试结果见表2。

表2 不同密封条件下各室洁净度

密封情况 未采取任何密封措施

密封门底部 密封整个门框

渗漏风量(m /h)

约200 约60

3

隔离走廊洁净度

低于9级

缓冲二洁净度 低于9级

主实验室洁净度

9

测试数据表明,在安全门未采取任何密封措施的情况下,各室洁净度均不能达到设计要求,将门框缝隙全部密封后,室内洁净度均达标。通过表

2还可以看出,门底部缝隙的渗漏风量占了全部渗漏风量的很大比例。因此,

在生物安全实验室施工中,一定要重视安全门的安装:

①安全门底部地板一定要水平,与门的缝隙要尽可能小,或者在门框平面的地面上设置一定高度的门槛;

②门框与门的平面要有足够的吻合度,加强门边缘的密封性; ③门关闭时与门框间要有足够的压紧力。

此外,可以考虑用密封性较好的不可开启式特种玻璃隔断来替代安全门,在发生事故时用挂在门旁墙上的安全锤打碎玻璃逃生,这种玻璃易粉碎且碎片无锐角,不会划伤人。

3 工况转换时的压差控制

生物安全实验室在工况转换或风机切换时出现正压或超负压问题是一个难点。类似问题还包括生物安全实验台开关机时由于排风机和送风机运行步调不一致所引起的室内压力超常等。

3.1 实验室稳态运行工况下的压差控制

为保证实验室的负压梯度尤其是污染区的负压梯度,生物安全实验室必须设置安全有效且反应灵敏的自动控制系统,对实验室的风量、压力按照一定的逻辑进行控制。文献[2][7]中详细介绍了多种控制方式。常见控制方式如图5(图中VAD 为变风量阀)所示。该控制方式采用变频风机和变风量阀共同控制送、排风量,能够实现复杂的负压控制过程和节能运行,但是这种控制方式存在多个控制对象和变量,使得控制逻辑复杂、系统繁琐。为了简化系统,人们在此基础上将送(或排)风阀改为定风量阀,取得了较好的效果,但是,当生物安全柜排风设备与主实验室共用排风管道,尤其是当室内设有大风量的排风设备时,这种控制方式将导致室内排风不足或风量失调。

综合上述分析,我们采用变风量和定风量相结合的控制方式(见图6,图中VAD 为变风量阀)。这种控制方式既可以设置为定送风量模式,也可以设定为定排风量模式运行。当设定为定送风量控制时,送风阀风量根据工况需要置为某一设定值,通过调节排风阀来控制室内压差;当设定为排风量控制时,排风阀风量根据工况需要置为某一设定值,通过调节送风阀来控制室内压差。在设计中,变风量阀均采用文丘里阀,此阀门的响应速度很快,动作时间在1s 之内,可满足系统对控制灵敏度的要求。

图5 常见控制方式 图6 本实验室控制方式

本实验室室内设置2台安全柜,正常情况下分四种运行工况,各工况下阀门设置值见表3。

表3 各工况阀门设置情况 单位:m 3/h

实验室送风阀

实验室排风阀

A2排风阀

B2送风阀

B2排风阀

定送风控制

0(关闭)450 0(关闭)

0(关闭)0(关闭)

0(关闭)0(关闭)

自动调节 自动调节

定排风控制

1377 1377 1377 1377

工况描述

安全柜全关 A2安全柜开 B2安全柜开 两安全柜全开

定送风 控制 1326 1326 1326 1326

定排风 控制 自动调节 自动调节 自动调节 自动调节

自动调节

自动调节

注:实验室送风阀“1326”表示在定送风量情况下20 ac/h换气次数下风量。

3.2 生物安全柜工况转换过程的压差控制

生物安全实验室的工况转换主要是安全柜的启闭引起的室内工况变化。在工况转换时,安全柜的状态变化使得室内风量重新分配,引起室内的压力变化。下面以定排风量控制方式为例,来说明工况转换过程的压差控制。本实验室采用的压差控制流程见图7。

实验室在某一工况下运行,当安全柜开启(或关闭)时,控制器接收到信号后对各文丘里阀发出相应工况的参数设置命令,在各阀门设置过程中,送风阀进行风量调节以维持室内正常压差。多次重复实验显示,在这种控制方案模式下,室内压差在工况转换过程中不出现明显压差波动,可以保持在设定压差波动±10Pa 范围内。

图7 安全柜启闭过程控制流程图 3.3 风机切换过程的压差控制

当某台排风机出现故障需要启动备用风机时,通常过程是风机出现故障,排风量减小,风机两端压力传感器检出信号,控制器关闭故障风机密闭阀,同时开启备用风机和密闭阀。从排风机出现故障到备用风机启动直至排风量达到一定值,室内总排风量将先减少然后随着备用风机的启动再慢慢增加,这一过程尽管只有数秒的时间,也将导致室内瞬时的正压。鉴于风机特性的制约,本课题组采取了两条主要措施解决该问题:一是排风机由传统的一用一备改为两用一备,减少风机故障切换时对室内压力的影响;二是风机切换过程中利用反应灵敏的文丘里阀进行压差控制,这样可以避免由于风机启动特性的差异导致的压力振荡。风机切换过程中的控制流程见图8。图中, 设定送风500m 3/h是通过实验所得出的单台风机运行时维持室内一定负压值所需要的送风量。

这种控制方式,有效的避免了风机切换时主实验室室内部出现的瞬时正压。控制过程见图10。

从图9看出,在控制系统设置控制条件前,主实验室图8 风机切换过程控制流程图 相对室外的压差高于零压(压差传感器量程为-100~

0Pa ,室内正压时显示0Pa ),且最大值高于缓冲二,形成气流外泄;设置控制条件后,主实验室相对室外最大压力为-25Pa 左右,且小于缓冲间,不会形成从主实验室到缓冲间的气流外泄,见图10。因此,主实验室在运行中一旦发生排风机故障切换时,设置了控制条件的系统能够保证主实验室空气不会泄漏到室外及缓冲二。

图10 本设计定排风量控制

图9 常规定排风量控制

5 结论

在三级实验室建设领域,国内在技术和认识方面还存在着不少问题,通过本次实验室设计和调试,我们对三级实验室的认识有所深入,本文主要针对一更正压保护、零压保护的研究与工况转换时压力梯度的保持方法进行了实验分析和总结,并得出如下结论:

1、一更正压保护有利于保证一更及与其直接相通房间的洁净度,而对主实验室的洁净度与零压保护相比并无显著影响;

2、安全门的密封性对主实验室的洁净度有显著影响,必须采取措施改善可开启安全门缝隙的密封效果;

3、采用定风量和变风量相结合的方法,通过调节文丘里阀的开度,能够在系统稳定运行和各种工况转换中保证各室间合理的压差梯度。

在建设过程中,我们还发现一些其它影响实验室安全性能的问题,如文丘里阀的特性与安装位置关系、不同类型的阀门动作时间的匹配、带送风的安全柜开启过程与实验室综合控制过程等,这些问题的解决还期待着生物安全实验室研究人员进一步研究和探讨。

参考文献:

[1] 中华人民共和国国务院令.病原微生物实验室生物安全管理条例。2004

[2] 涂光备,邢金城,凌继红。医院建筑空调净化与设备。北京:中国建筑工业出版社,2005 [3] 刘江,胡国华.三级生物安全实验室通风中的问题及改进方法.中国卫生工程学,2006.10(5):287-289

[4] 中华人民共和国建设部.GB50346-2004 生物安全实验室建设技术规范[S].北京:中国建筑工业出版社,2004

[5] 中华人民共和国国家质量监督检验检疫总局,中国国家标准化管理委员会.GB19489-2004 实验室生物安全通用要求,北京:中国建筑工业出版社,2004 [6] 牛维乐,刘华.生物安全三级实验室气流控制.洁净与空调技术,2003(4):5-8 [7] 许钟麟,王清勤.生物安全实验室与生物安全柜.北京:中国建筑工业出版社,2004 [8] 曹国庆,刘华等.由生物安全实验室检测引发的有关设计问题的几点思考.暖通空调,2007(10):52-57

[9] ASHRAE.Health and facilities [M]//ASHRAE Applications Handbook, 1999

附:作者信息

黄征:男,1967年06月,江苏省苏净集团有限公司,电话:0512-68254699,苏州市新区玉山路55号,(215011) 王力:同上。

李江龙:天津大学环境学院在读硕士,电话:022-27890555,天津市南开区卫津路92号天津大学环境学院24楼B508,(300072)。

凌继红:天津大学环境学院,电话:022-27890555,天津市南开区卫津路92号天津大学环境学院24楼B508,(300072)。 邢金城:同上。 涂光备:同上。 周志航:同上。

影响三级生物安全实验室性能的相关问题研究

黄征 李江龙 王力 凌继红 邢金城 周志航 涂光备

1 江苏苏净集团 2 天津大学环境学院

摘 要 本文对三级生物安全实验室中一更压力和安全门密封性对主实验室洁净度的影响,以及实验室运行工况转换与排风机故障切换时保持合理压力梯度的手段等问题进行了分析研究。通过实验总结出:一更保持非负压状态即可不影响主实验室的洁净度,而安全门的密封性对实验室污染区洁净度影响很大;采用设置在送风阀风量突变条件的定排风量控制,在工况转换和风机故障切换时能够维持实验室合理的压力梯度。

关键词 生物安全实验室 正压保护 工况转换 风机切换 定排风量控制

1

2

1

2

2

2

2

Research of the Problems that Affect the Capability of

Level-3 Biosafety Laboratory

By Huang Zheng, Li Jianglong, Wang Li, Ling Jihong, Xing jincheng, Zhou Zhihang and Tu Guangbei

Abstract The article summarizes the research process of the positive (or common) pressure protection in First Changeroom and the airproof of exit door, which may influence the indoor cleanliness, and also gives some methods on how to maintain the pressure gradient when the operation condition changes and the exhaust fan switches affected by sudden malfunction. One conclusion is that the pressure of First Changeroom has no influence on the cleanliness of the main room, but the airproof of exit door affects the indoor cleanliness badly, so a good airproof exit door is necessary. The Other conclusion is that by the help of the control system that keeps exhaust volume constant and decreases the supply air fast with the rising of indoor pressure, the reasonable pressure gradient in contaminative zone can be maintained when the operation condition changes or the exhaust fan switches.

Keywords Level-3 Boisafety Laboratory, Positive pressure protection, Operation condition change, Fan switch, Constant exhaust volume control

1 引言

2003年SARS 病毒大流行后,我国生物安全实验室的建设出现了前所未有的发展。国家陆续发布了关于微生物实验室建设与管理的相关条例与规范,并建立了实验室国家认可制度。2004年施行的《病原微生物实验室生物安全管理条例》[1]规定:可以进行高致病性病原微生物实验活动的三、四级生物安全实验室必须满足下述要求:①符合国家生物安全实验室建筑技术规范;②通过实验室国家认可;③工程质量经建筑主管部门依法检测验收合格。

相关资料统计,目前,我国已建成和在建的三级生物安全实验室有上百家,而通过实验室国家认可的三级实验室仅16家,大部分实验室在建成后不能通过国家认可,究其原因

主要有两点:一方面,建筑设计或承建单位对生物安全实验室的认识不足,致使设计施工过程中存在一些缺陷,另一方面,生物安全实验室压差控制策略还存在着一些有待突破的难点。鉴于此,苏净集团和天津大学依据共同承担的江苏省科技攻关课题,建造了一个1:1的生物安全实验室模型,对三级生物安全实验室施工及压差控制中存在的一些问题进行了研究。本文仅针对实验室的洁净度和压差控制问题进行探讨如下,希望在三级生物安全实验室建设和运行方面能为相关单位提供一些参考。

22

本课题组搭建的模型实验室总面积150m ,其中主实验室面积26m ,其余为辅助用房,包括参观走廊、监控室、洗消间、换鞋间、一更、淋浴间、二更、缓冲一、隔离走廊、缓冲二等,洁净度等级除主实验室为ISO 7级外,其余房间均为ISO 8级[2],[3],[4],[5]。平面布局如图1

所示。

图1 三级生物安全实验室平面布局图

2 洁净度的控制

在负压洁净室内,除了过滤器的过滤效率和气流分布[6]外,影响室内洁净度的主要因素是换气次数和由非洁净区渗入的空气量。在相同的换气次数下,由非洁净区渗入的风量越小,对室内洁净度越有利。对于生物安全实验室区域,来自非洁净区的渗入风量主要通过一更门和安全门进入,因此,我们重点对这两个方面进行了实验研究。 2.1 正压保护与零压保护对洁净度的影响

在实验室的平面布局中,实验室洁净区域通过一更与非洁净区连通。一更的负压将增加渗入室内的空气量,进而影响室内的洁净度,因此,人们通常将一更相对于非洁净区的压力设置为微正压或零压以阻止室外未经净化的空气渗入洁净区,称为正压或零压保护。相关参考文献[7],[8]认为,正压隔离对主实验室的洁净度更为有利。为了对比正压保护和零压保护的效果,我们分别对一更正压和零压情况下各房间的室内粒子浓度进行了多次检测,主要房间检测结果见表1、图2~4。

表1 正压和零压保护下主要房间粒子浓度的测试值 单位: pcs/m3房间名称 主实验室 缓冲一 二更

工 况 正压 零压 正压 零压 正压 零压

0.3um 0.5um 1um 35336 31449 26502 38163 65018 73145

2um 23322 24735 20495 31802 53710 55830

3um 9894 14488

11307 15194 25442

32862

5um 1060 1060 2473 2473 3180 6007

197173 195406 135689 315194 178799 162898 342049 225795

图2 主实验室各粒径粒子浓度 图3 缓冲一各粒径粒子浓度

图4 二更各粒径粒子浓度

从测试数据可以看出,在一更相对于非洁净区为零压的情况下,二更和缓冲一测得的空气各粒径粒子浓度比在一更保持正压情况下大,而主实验室由于与外界有多重缓冲,各粒径粒子浓度在两种工况下相差不大,即一更的正压和零压仅影响相邻的二更和缓冲二的室内粒子浓度,但是对主实验室的空气洁净度不产生显著影响,由此可见,一更采取正压保护的观点,有待进一步研究和商榷。

2.2 安全门的密封性对实验室洁净度的影响

基于消防安全方面考虑,三级生物安全实验室须在半污染区设置安全通道(即安全门)作为紧急出口。安全门一般设置在隔离走廊,距离主实验室较近,由于隔离走廊的负压较大(-30Pa ),导致大量未经过滤的室外空气经安全门渗入室内,不仅影响了隔离走廊的洁净度,还影响到缓冲二和主实验室的洁净度。我们在主实验室换气次数为20 AC/h,安全门采用不同的密封措施下分别对隔离走廊、缓冲二、主实验室进行了洁净度测试,测试结果见表2。

表2 不同密封条件下各室洁净度

密封情况 未采取任何密封措施

密封门底部 密封整个门框

渗漏风量(m /h)

约200 约60

3

隔离走廊洁净度

低于9级

缓冲二洁净度 低于9级

主实验室洁净度

9

测试数据表明,在安全门未采取任何密封措施的情况下,各室洁净度均不能达到设计要求,将门框缝隙全部密封后,室内洁净度均达标。通过表

2还可以看出,门底部缝隙的渗漏风量占了全部渗漏风量的很大比例。因此,

在生物安全实验室施工中,一定要重视安全门的安装:

①安全门底部地板一定要水平,与门的缝隙要尽可能小,或者在门框平面的地面上设置一定高度的门槛;

②门框与门的平面要有足够的吻合度,加强门边缘的密封性; ③门关闭时与门框间要有足够的压紧力。

此外,可以考虑用密封性较好的不可开启式特种玻璃隔断来替代安全门,在发生事故时用挂在门旁墙上的安全锤打碎玻璃逃生,这种玻璃易粉碎且碎片无锐角,不会划伤人。

3 工况转换时的压差控制

生物安全实验室在工况转换或风机切换时出现正压或超负压问题是一个难点。类似问题还包括生物安全实验台开关机时由于排风机和送风机运行步调不一致所引起的室内压力超常等。

3.1 实验室稳态运行工况下的压差控制

为保证实验室的负压梯度尤其是污染区的负压梯度,生物安全实验室必须设置安全有效且反应灵敏的自动控制系统,对实验室的风量、压力按照一定的逻辑进行控制。文献[2][7]中详细介绍了多种控制方式。常见控制方式如图5(图中VAD 为变风量阀)所示。该控制方式采用变频风机和变风量阀共同控制送、排风量,能够实现复杂的负压控制过程和节能运行,但是这种控制方式存在多个控制对象和变量,使得控制逻辑复杂、系统繁琐。为了简化系统,人们在此基础上将送(或排)风阀改为定风量阀,取得了较好的效果,但是,当生物安全柜排风设备与主实验室共用排风管道,尤其是当室内设有大风量的排风设备时,这种控制方式将导致室内排风不足或风量失调。

综合上述分析,我们采用变风量和定风量相结合的控制方式(见图6,图中VAD 为变风量阀)。这种控制方式既可以设置为定送风量模式,也可以设定为定排风量模式运行。当设定为定送风量控制时,送风阀风量根据工况需要置为某一设定值,通过调节排风阀来控制室内压差;当设定为排风量控制时,排风阀风量根据工况需要置为某一设定值,通过调节送风阀来控制室内压差。在设计中,变风量阀均采用文丘里阀,此阀门的响应速度很快,动作时间在1s 之内,可满足系统对控制灵敏度的要求。

图5 常见控制方式 图6 本实验室控制方式

本实验室室内设置2台安全柜,正常情况下分四种运行工况,各工况下阀门设置值见表3。

表3 各工况阀门设置情况 单位:m 3/h

实验室送风阀

实验室排风阀

A2排风阀

B2送风阀

B2排风阀

定送风控制

0(关闭)450 0(关闭)

0(关闭)0(关闭)

0(关闭)0(关闭)

自动调节 自动调节

定排风控制

1377 1377 1377 1377

工况描述

安全柜全关 A2安全柜开 B2安全柜开 两安全柜全开

定送风 控制 1326 1326 1326 1326

定排风 控制 自动调节 自动调节 自动调节 自动调节

自动调节

自动调节

注:实验室送风阀“1326”表示在定送风量情况下20 ac/h换气次数下风量。

3.2 生物安全柜工况转换过程的压差控制

生物安全实验室的工况转换主要是安全柜的启闭引起的室内工况变化。在工况转换时,安全柜的状态变化使得室内风量重新分配,引起室内的压力变化。下面以定排风量控制方式为例,来说明工况转换过程的压差控制。本实验室采用的压差控制流程见图7。

实验室在某一工况下运行,当安全柜开启(或关闭)时,控制器接收到信号后对各文丘里阀发出相应工况的参数设置命令,在各阀门设置过程中,送风阀进行风量调节以维持室内正常压差。多次重复实验显示,在这种控制方案模式下,室内压差在工况转换过程中不出现明显压差波动,可以保持在设定压差波动±10Pa 范围内。

图7 安全柜启闭过程控制流程图 3.3 风机切换过程的压差控制

当某台排风机出现故障需要启动备用风机时,通常过程是风机出现故障,排风量减小,风机两端压力传感器检出信号,控制器关闭故障风机密闭阀,同时开启备用风机和密闭阀。从排风机出现故障到备用风机启动直至排风量达到一定值,室内总排风量将先减少然后随着备用风机的启动再慢慢增加,这一过程尽管只有数秒的时间,也将导致室内瞬时的正压。鉴于风机特性的制约,本课题组采取了两条主要措施解决该问题:一是排风机由传统的一用一备改为两用一备,减少风机故障切换时对室内压力的影响;二是风机切换过程中利用反应灵敏的文丘里阀进行压差控制,这样可以避免由于风机启动特性的差异导致的压力振荡。风机切换过程中的控制流程见图8。图中, 设定送风500m 3/h是通过实验所得出的单台风机运行时维持室内一定负压值所需要的送风量。

这种控制方式,有效的避免了风机切换时主实验室室内部出现的瞬时正压。控制过程见图10。

从图9看出,在控制系统设置控制条件前,主实验室图8 风机切换过程控制流程图 相对室外的压差高于零压(压差传感器量程为-100~

0Pa ,室内正压时显示0Pa ),且最大值高于缓冲二,形成气流外泄;设置控制条件后,主实验室相对室外最大压力为-25Pa 左右,且小于缓冲间,不会形成从主实验室到缓冲间的气流外泄,见图10。因此,主实验室在运行中一旦发生排风机故障切换时,设置了控制条件的系统能够保证主实验室空气不会泄漏到室外及缓冲二。

图10 本设计定排风量控制

图9 常规定排风量控制

5 结论

在三级实验室建设领域,国内在技术和认识方面还存在着不少问题,通过本次实验室设计和调试,我们对三级实验室的认识有所深入,本文主要针对一更正压保护、零压保护的研究与工况转换时压力梯度的保持方法进行了实验分析和总结,并得出如下结论:

1、一更正压保护有利于保证一更及与其直接相通房间的洁净度,而对主实验室的洁净度与零压保护相比并无显著影响;

2、安全门的密封性对主实验室的洁净度有显著影响,必须采取措施改善可开启安全门缝隙的密封效果;

3、采用定风量和变风量相结合的方法,通过调节文丘里阀的开度,能够在系统稳定运行和各种工况转换中保证各室间合理的压差梯度。

在建设过程中,我们还发现一些其它影响实验室安全性能的问题,如文丘里阀的特性与安装位置关系、不同类型的阀门动作时间的匹配、带送风的安全柜开启过程与实验室综合控制过程等,这些问题的解决还期待着生物安全实验室研究人员进一步研究和探讨。

参考文献:

[1] 中华人民共和国国务院令.病原微生物实验室生物安全管理条例。2004

[2] 涂光备,邢金城,凌继红。医院建筑空调净化与设备。北京:中国建筑工业出版社,2005 [3] 刘江,胡国华.三级生物安全实验室通风中的问题及改进方法.中国卫生工程学,2006.10(5):287-289

[4] 中华人民共和国建设部.GB50346-2004 生物安全实验室建设技术规范[S].北京:中国建筑工业出版社,2004

[5] 中华人民共和国国家质量监督检验检疫总局,中国国家标准化管理委员会.GB19489-2004 实验室生物安全通用要求,北京:中国建筑工业出版社,2004 [6] 牛维乐,刘华.生物安全三级实验室气流控制.洁净与空调技术,2003(4):5-8 [7] 许钟麟,王清勤.生物安全实验室与生物安全柜.北京:中国建筑工业出版社,2004 [8] 曹国庆,刘华等.由生物安全实验室检测引发的有关设计问题的几点思考.暖通空调,2007(10):52-57

[9] ASHRAE.Health and facilities [M]//ASHRAE Applications Handbook, 1999

附:作者信息

黄征:男,1967年06月,江苏省苏净集团有限公司,电话:0512-68254699,苏州市新区玉山路55号,(215011) 王力:同上。

李江龙:天津大学环境学院在读硕士,电话:022-27890555,天津市南开区卫津路92号天津大学环境学院24楼B508,(300072)。

凌继红:天津大学环境学院,电话:022-27890555,天津市南开区卫津路92号天津大学环境学院24楼B508,(300072)。 邢金城:同上。 涂光备:同上。 周志航:同上。


相关内容

  • 江西省医疗机构临床实验室管理办法实施细则
  • 江西省医疗机构临床实验室管理办法实施细则 第一章 总 则 第一条 为加强我省医疗机构临床实验室的建设与管理,提高临床检验水平,保证医疗质量和医疗安全,根据<医疗机构临床实验室管理办法>,结合我省实际,制定本实施细则. 第二条 本细则所称医疗机构临床实验室是指对取自人体的各种标本进行生物学 ...

  • 杭州太仁堂生物科技股份有限公司商业计划书
  • 杭州太仁堂生物科技股份有限公司 商业计划书 目 录 一.公司简介 ....................................................... 3 1.1 公司基本情况 ................................................ ...

  • 2015年度湖南省科技计划项目申报指南
  • 附件1: 2015年度湖南省科技计划项目申报指南 围绕全省经济社会发展的重大需求,坚持问题导向,按照主动跟进.有所为有所不为的原则,选择年度支持重点和方向,制定本计划项目申报指南. 本指南是组织编制与实施2015年度省科技计划项目的主要依据,也是各级科技管理部门.项目申报单位.项目申报者组织申报本年 ...

  • 化妆品的感官评价
  • 化妆品的感官评价与流变学性质的关系 化妆品的感官质量是决定化妆品受消费者喜爱程度的重要方面.如何确定可测定的某些物理性质和一般消费者感官反应之间的相关性,是化妆品质量评价的重要问题.其中较为重要的是感官评价与流变性质的关系.感官评价包括取样.涂抹和用后感觉几个阶段. 流变性质包括黏度.屈服值.流变曲 ...

  • 实验室等级划分
  • 实验室生物安全防护实验室是指: 实验室的结构和设施.安全操作规程.安全设备能够确保工作人员在处理含有致病微生物及其毒素时,不受实验对象侵染,周围环境不受污染.根据微生物及其毒素的危害程度不同,分为四级,一级最低,四级最高.生物安全防护一级实验室一般适用于对健康成年人无致病作用的微生物:二级适用于对人 ...

  • 体外诊断试剂生产质量体系检查要点指南2013
  • 体外诊断试剂生产质量体系检查要点指南 (2013版) 按照医疗器械管理的体外诊断试剂是一类特殊的产品,包括可单独使用或与仪器.器具.设备或系统组合使用,在疾病的预防.诊断.治疗监测.预后观察.健康状态评价以及遗传性疾病的预测过程中,用于对人体样本(各种体液.细胞.组织样本等)进行体外检测的试剂.试剂 ...

  • 生物专业毕业论文
  • 国防工业职业技术学院 毕业设计(论文) 题 目 :现代微生物技术在废水处理 中的应用 培养部门 xxxxxxxx 专业名称 生物技术及应用 学生姓名 xx 学号 xxxxxxxxxxx 导师姓名 摘 要 从人类的诞生开始就存在着人与环境的对立统一关系.从古至今,随着人类社会的发展,环境问题也在发生着 ...

  • 东莞户籍自主参训补贴项目及补贴标准
  • 自主参训补贴项目及补贴标准 (第一版) 证书 类别 级别 补贴金额 ( 元) 系列 高等学校教师 中等专业学校教师 中学教师 小学(幼儿园) 教师 中学二级教师 专业技术资格. 专业技术资格.职(执)业资格名称 助教 助理讲师 中学三级教师 小学一级教师 幼儿园一级教师 助理讲师 技工学校教师 二级 ...

  • 国家重大科技基础设施建设中长期规划
  • 国务院印发国家重大科技基础设施建设中长期规划 http://www.eastmoney.com/2013年03月04日 18:02 国务院关于印发国家重大科技基础设施建设中长期规划(2012-2030年)的通知 国发[2013]8号 各省.自治区.直辖市人民政府,国务院各部委.各直属机构: 现将&l ...